ARMAFLEX 520 Specially formulated adhesive developed for ArmaFlex insulation materials. Material type Contact adhesive on polychloroprene basis, free of aromatic components. Colour Beige Material special info Liquid Applications Gluing of all flexible ArmaFlex insulation materials (except HT/ArmaFlex & ArmaFlex Ultima). Special features Specially formulated adhesive for uniform and safe seam bonding of ArmaFlex insulation materials. Assembly Please observe our installation instructions/product data sheets. Application temperature: ideally +20˚C, not below 0˚C. At temperatures below +5˚C or high humidity approx above 80%), increased condensation may form on the surfaces to be glued or adhesive films. In these cases bonding is poor or impossible. This can be tested by using absorbent paper (blotting or crepe paper). Work should not be carried out on operating plant or areas exposed to strong sunlight. Shake and stir well before use. Apply thinly to the areas to be bonded with a brush or spatula. For contact adhesion press together with force during the contact adhesion time. Detailed application guidance is available. Remarks The adhesive achieves its final strength after 36 hours. Only then should plant be put into operation. Never insulate plant which is in operation or work in strong sunlight. Wait 36 hours before applying coatings (exception: ArmaFinish 99), adhesive tape, coverings etc. ARMAFLEX RS850 Non-drip one component adhesive in gel form. Specifically developed for ArmaFlex insulation materials based on synthetic rubber. Material type Thixotropic contact adhesive on polychloroprene basis. Colour Beige Material special info Gel form Applications Application on pipes, ducts and tanks with service temperature up to +70˚C. Gluing of all flexible ArmaFlex insulation materials (except HT/ArmaFlex & ArmaFlex Ultima). Special features Specially formulated adhesive for uniform and safe seam bonding of ArmaFlex insulation materials. Assembly Please observe our installation instructions/product data sheets. Application temperature: ideally +20˚C, not below 0˚C. At temperatures below +5˚C or high humidity approx above 80%), increased condensation may form on the surfaces to be glued or adhesive films. In these cases bonding is poor or impossible. This can be tested by using absorbent paper (blotting or crepe paper). Work should not be carried out on operating plant or areas expossed to strong sunlight. Shake and stir well before use. Apply thinly to the areas to be bonded with a brush or spatula. For contact adhesion press together with force during the contact adhesion time. Detailed application guidance is avalable. Remarks The adhesive achieves its final strength after 24 hours. The system should never be operated during this time and any self-adhesive tape or protective coating (exception: ArmaFinish 99), should only be applied after the time has elapsed. ARMAFLEX ADHESIVES TECHNICAL DATA 228